kb:ni-hardware:daq-mx [2022/06/20 10:02] – created manuel.sebaldkb:ni-hardware:daq-mx [2024/01/17 12:29] (current) joerg.hampel
Line 1: Line 1:
-====== 20 NI DAQmx ======+====== 21 NI DAQmx ======
  
-Learnings and best practices from working with NI DAQmx hardware.+//Learnings and best practices from working with NI DAQmx hardware.//
  
  
Line 15: Line 15:
  
   - Reset the MAX database. From the KB article: From within NI MAX, select Tools » Reset Configuration Data. Confirm the warning dialog with "Yes".   - Reset the MAX database. From the KB article: From within NI MAX, select Tools » Reset Configuration Data. Confirm the warning dialog with "Yes".
 +  - Reconfigure all needed device (especially the device names) DAQmx tasks.
 +  - If MAX doesn't start anymore, refer to the [[https://forums.ni.com/t5/Example-Code/MAX-Database-Corruption-Removal-Tool/ta-p/3521466?profile.language=en|MAX Database Corruption Removal Tool]] or [[https://knowledge.ni.com/KnowledgeArticleDetails?id=kA03q000000YHcVCAW&l=de-DE|reset manually]].
  
 <note important>By resetting the MAX database, all configured devices and DAQmx tasks will be reset, too.</note> <note important>By resetting the MAX database, all configured devices and DAQmx tasks will be reset, too.</note>
- 
-  - Reconfigure all needed device (especially the device names) DAQmx tasks. 
- 
  
 ==== Symptoms ==== ==== Symptoms ====
  
-The following can errors indicate a problem with the MAX database. Check MAX if one of these errors occur.+The following errors can indicate a problem with the MAX database. Check the MAX if one of these errors occur.
  
   * Error code -229771 "Internal Software Error occurred in MIG software. Please contact National Instruments Support." \\ (e.g. in DAQmx Create Scale (Linear).vi)   * Error code -229771 "Internal Software Error occurred in MIG software. Please contact National Instruments Support." \\ (e.g. in DAQmx Create Scale (Linear).vi)
 +  {{ :kb:ni-hardware:error_-229771.png |}}
 +  * Application hangs during "Discover hardware" (or MAX doesn't start anymore)
  
kb/ni-hardware/daq-mx.1655719375.txt.gz · Last modified: 2022/06/20 10:02 by manuel.sebald